Each incinerator shall be supplied with all necessary assembly/disassembly tools.
Spare parts and consumables The proposed incinerator systems shall include all
necessary spare parts, PPE, and consumables required for 2 years of operation.
Incinerator Items/Model |
HICLOVER YD30(PLC) |
Burn Rate (Average) |
30-50kg/hour(Medical Waste) 10-15kg/hour(Pet Animal Cremation) |
Feed Capacity(Average) |
40kg/feeding |
Control Mode |
PLC Automatic |
Primary Combustion Chamber |
360L(0.36M3) |
Internal Dimensions |
100x60x60cm |
Secondary Chamber |
200L |
Smoke Filter Chamber |
Yes |
Feed Mode |
Manual |
Voltage |
220V |
Power |
0.8Kw |
Burner Type |
Italy Brand |
Oil Consumption (kg/hour) |
12 |
N.Gas Consumption (m3n/hour) |
9.8–20 |
Temperature Monitor |
Yes |
Temperature Thermometer |
Corundum Probe Tube, 1400℃Rate. |
The supplier is to provide a proposed list of spare parts for the incinerators.
Mandatory spare parts must include as a minimum.
The forecasted feedstock loads, and daily loading rates are generally summarized as
• Mixed general, clinical and incinerable hazardous wastes with a wide range
of calorific values and densities. The majority of the wastes will be of a general
municipal nature, with up to 15% by volume of medical wastes and up to 5% by
volume of incinerable hazardous wastes. The content of the combustible matter will be above 60% and moisture content below 30%. The wastes will be crudely pre-mixed by selective loading from different waste
streams prior to incinerator loading.
• Wastes either small enough to fit within a 60 litre waste sack or broken
up or shredded to less than 300mm in size.
• Operation on a daytime shift basis, 5 days per week.
• An 8 hour daily operating cycle of ash removal, pre-heat and burn with
continuous loading if required. The automated burn completion and cool
down cycle will take place overnight.
• The incinerators shall be capable of using diesel fuel as a supplemental
fuel while the associated management equipment shall be capable of using electricity as the primary power source
• Also consider provision for meeting international emission standards.
Able to handle an average waste production of 600kg/day
“• Minimum load capacity: 100 kg
https://www.tiktok.com/@wasteincinerators/video/7147354941236153646?is_from_webapp=1&sender_device=pc&web_id=7114539833770739242
• Maximum load capacity: 300 kg
• Nominal burning rate: 70 – 120 kg/hr (= 560 – 960 kg per 8hour day)
All incinerators shall meet the following emission and operating standards:
• Combustion efficiency (C.E.) shall be at least 99.0%
• The combustion efficiency shall be computed as follows:
o C.E = (CO2 X 100) / (%CO2 +%CO)
Suitably designed pollution control devices such as scrubbers, filters or
electrostatic precipitators, shall be installed/retrofitted with the incinerator to achieve emission limits.”